Regency Indoor Fireplace P48 LP2 User Guide

Gas Fireplaces  
P48 Gas Fireplace  
P48 Zero Clearance Direct Vent Gas Fireplace  
Model  
P48-NG2  
P48-LP2  
Fuel Type  
Natural Gas  
Propane  
Minimum Supply Pressure  
Manifold Pressure - High  
Manifold Pressure - Low  
Orifice Size  
5” W.C. (1.25 kPa)  
3.8” W.C. (0.95 kPa)  
1.1” W.C. (0.27 kPa)  
#27 DMS - 0-4500ft  
29,000 BTU/h (8.49 kW)  
51,000 BTU/h (14.94 kW)  
5” Inner / 8” Outer  
12” W.C. (3.00 kPa)  
11” W.C. (2.74 kPa)  
3.3” W.C. (0.82 kPa)  
#47 DMS  
Minimum Input  
26,000 BTU/h (3.07 kW)  
48,000 BTU/h (6.30 kW)  
5” Inner / 8” Outer  
Maximum Input  
Vent Sizing  
Approved Venting Systems  
Flex Vent Systems:  
FPI AstroCap™ Flex Vent  
Rigid Pipe Vent Systems:  
Simpson Dura-Vent® Direct Vent GS  
B
A
L
C D  
F
Top Header  
Drywall  
(or other  
facing)  
H
E
A
11" (279mm)  
dia. Hole through  
wall Vent.  
Unit Dimensions  
Description  
P33  
A
B
C
D
E
F
Front Face Width  
Rear Firebox Width  
Front Face Height  
Height w/ Standoff  
Unit Depth  
48” (1219mm)  
34-1/2” (876mm)  
41” (1041mm)  
47” (1193mm)  
23-1/4” (324mm)  
40” (1016mm)  
G
I
M
Firebox Height  
Framing Dimensions Description  
P33  
J
G
Framing Width  
48-1/2” (1232mm)  
47-1/2” (1207mm)***  
H***  
Framing Height***  
29-3/4” (756mm) Vertical Rise  
I
Framing Depth  
26-1/4” (667mm) No Vertical Rise  
N
J
Corner Wall Length  
57-5/8” (1464mm)  
81-1/2” (2070mm)  
K
Corner Facing Wall Width  
Framed Chase Ceiling  
O
P
K
N/A - Vertical Rise  
50” (1270mm) No Vertical Rise  
Opening for gas  
connection  
L
M
Vent Centerline Height  
43” (1092mm)  
N
O
P
Gas Connection Height  
Gas Connection Inset  
Gas Connection Width  
2” (51mm)  
3-3/4” (95mm)  
5” (127mm)  
Please refer to Page 11 (Exterior Vent Terminations)  
for additional guidelines on vent locations.  
***Important: Framing height requires consideration of the hearth  
depth. Dimension H = H + the thickness of installed hearth.  
June 2007 Regency Product Specifications Book  
61  
 
Gas Fireplaces  
P48 Gas Fireplace  
Regency Direct Vent System (Flex)  
Snorkel Terminations  
Horizontal Terminations Only  
Snorkel Terminations:  
These venting systems, in combination with the P48 Direct Vent Gas  
Fireplace, have been tested and listed as a direct vent heater system  
by Warnock Hersey. The location of the termination cap must conform  
to the requirements in the Vent Terminal Locations diagram.  
For installations requiring a vertical rise on the exterior of the building, 14-  
inch and 36-inch tall Snorkel Terminations are available. Follow the same  
installation procedures as used for standard Horizontal Termination.  
NEVER install the snorkel upside down.  
FPI Direct Vent (Flex) System Termination Kits include all the parts  
needed to install the P48 using a flexible vent.  
FPI Kit #  
Length Contains:  
#946-618  
6 Feet  
1) 6-5/8” flexible liner (Kit length)  
2) 4” flexible liner (Kit length)  
3) spring spacers (3)  
Dura-Vent  
Snorkel  
4) thimble (2)  
5) AstroCap termination cap (1)  
6) screws (12)  
#946-616  
10 Feet  
7) tube of Mill Pac (1)  
8) plated screws (8)  
Min. 12"*  
(305mm)  
9) S.S. screws #8 x 1-1/2” drill point, (4)  
10) vinyl siding standoff  
Notes:  
1) Liner sections should be continuous without any joints or seams.  
2) Only Flex pipe purchased from Regency may be used for Flex  
installations.  
3) Horizontal sections must be supported every 3 feet.  
AstroCap XL  
(Part# 946-623/P)  
Below Grade Snorkel Installation (Dura-Vent Only)  
If the Snorkel Termination must be installed below grade, i.e. basement  
application, proper drainage must be provided to prevent water from  
entering the Snorkel Termination. Refer to Rigid Pipe Installation  
instructions for details. Do not attempt to enclose the Snorkel within the  
wall, or any other type of enclosure.  
Vinyl Siding  
Standoff  
Wall Thimble  
5” dia.  
Flue pipe  
8" dia.  
Flue pipe  
Spring Spacer  
Dura-Vent  
Snorkel  
Alternate Horizontal  
Termination Caps  
Alternate Snorkel  
Termination Cap  
Part #1282 (14”)  
Part #1281 (36”)  
Window  
Well  
Adequate  
drainage  
Gravel  
If required by the external termination location the listed  
alternate termination caps may be used. (Refer to Page 11)  
June 2007 Regency Product Specifications Book  
63  
 
Gas Fireplaces  
P48 Gas Fireplace  
Rigid Pipe Venting  
Horizontal or Vertical Terminations  
Vertical  
Terminal  
2
4
8
14  
0
6
10  
12  
Storm Collar  
Flashing  
Vinyl Siding  
Standoff  
40  
38  
36  
34  
32  
Horizontal  
Termination Cap  
# 946-623/P  
Ceiling Firestop  
Wall Thimble  
Adj.Pipe Length  
Pipe Length  
11" - 14-5/8”  
Horizontal  
Termination Cap  
# 946-623/P  
90o Elbow  
24" Length  
Vinyl Siding  
Standoff  
Wall Thimble  
Adj.Pipe Length  
30  
28  
11" - 14-5/8”  
45o Elbow  
Rigid Pipe Adapter  
# 770-994  
Alternate Horizontal  
Termination Caps  
26  
24  
Alternate Snorkel  
Termination Cap  
Part #1282 (14”)  
Part #1281 (36”)  
22  
20  
18  
16  
14  
12  
10  
If required by the external termination location the listed  
alternate termination caps may be used. (Refer to Page 11)  
Venting Arrangements - Vertical  
Terminations  
Rigid Pipe System  
(Propane & Natural Gas)  
The P48 is approved for a maximum 40 ft. straight vertical, with Rigid  
Pipe vent systems for Propane and Natural Gas.  
The lightly shaded area,  
, in the diagram shows allowable venting  
configurations with a maximum two 45° elbows allowed.  
The darker shaded area,  
, in the diagram shows allowable venting  
8
6
configurations using 45° and one 90° elbow.  
Vent must be supported at offsets.  
Horizontal sections must be supported every 3 feet.  
Firestops are required at each floor level and whenever  
passing through a wall.  
4
2
0
Maintain clearances to combustible materials.  
Minimum of 1’ pipe section between elbows.  
Note: Must use optional flue adapter when using Rigid Pipe (Part  
# 770-994).  
Max. 10’ (3m)(centerline to centerline)  
Minimum 12” (305mm)  
64  
June 2007 Regency Product Specifications Book  
 
Gas Fireplaces  
P48 Gas Fireplace  
Vertical Venting with Two (2) 90° Elbows  
- Initial vertical section.  
Vertical Venting with Three (3) 90°  
Elbows - Initial vertical section.  
Two 45° elbows = One 90° elbow  
Two 45° elbows = One 90° elbow  
Option  
A)  
V
H
V+ V1  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
6’ Min.  
Maximum total pipe: length, of  
all sections, must not exceed  
30 feet.  
Option  
A)  
V
H + H1  
3’ Max.  
4’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
8’ Max.  
V+ V1  
4’ Min.  
6’ Min.  
7’ Min.  
8’ Min.  
9’ Min.  
10’ Min.  
Maximum total pipe: length, of  
all sections, must not exceed  
30 feet.  
1’ Min.  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
4’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
8’ Max.  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
6’ Min.  
7’ Min.  
Total horizontal sections must  
not exceed 8 feet.  
Total horizontal sections must  
not exceed 8 feet.  
B)  
B)  
C)  
C)  
Minimum of 1 foot between  
90° elbows is required.  
Minimum of 1 foot between  
90° elbows is required.  
D)  
D)  
E)  
E)  
F)  
Vertical Venting with Two (2) 90° Elbows  
- Initial horizontal section.  
Vertical Venting with Three (3) 90°  
Elbows - Initial horizontal section.  
Two 45° elbows = One 90° elbow  
Two 45° elbows = One 90° elbow  
Option  
A)  
H + H1  
2’ Max.  
3’ Max.  
4’ Max.  
5’ Max.  
6’ Max.  
V
Maximum total pipe: length, of  
all sections, must not exceed  
30 feet.  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
6’ Min.  
Option  
A)  
H
V
H + H1  
3’ Max.  
4’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
V+ V1 Maximum total pipe:  
Total horizontal sections must  
not exceed 6 feet.  
Minimum of 1 foot between  
90° elbows is required.  
B)  
length, of all sections,  
1’ Max.  
2’ Max.  
3’ Max.  
4’ Max.  
5’ Max.  
1’ Min.  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
3’ Min.  
5’ Min.  
7’ Min.  
9’ Min.  
11’ Min.  
must not exceed 30  
feet.  
C)  
B)  
Total horizontal sections  
must not exceed 7  
feet.  
D)  
E)  
C)  
Minimum of 1 foot  
between 90° elbows  
is required.  
D)  
E)  
June 2007 Regency Product Specifications Book  
 
65  
Gas Fireplaces  
P48 Gas Fireplace  
Maintain clearances to combustibles.  
Venting Arrangements - Horizontal  
Terminations  
Horizontal vent must be supported every 3 feet.  
Firestops are required at each floor level and whenever passing  
through a wall.  
This diagram shows all allowable combinations of vertical runs with  
horizontal terminations, using one 45° and one 90° elbow (two 45º  
elbows equal one 90° elbow).  
Avent guard should be used whenever the termination is lower than the  
specified minimum or as per local codes.  
Note: Must use optional flue adapter (Part # 770-994) when using  
Rigid Pipe.  
Note: FPIDirectVentSystem(Flex)isonlyapprovedforhorizontal  
terminations.  
Horizontal (Feet)  
8
0
2
4
6
18  
20  
16  
10  
12  
14  
16  
14  
12  
10  
8
6
4
43” (1092mm)  
Minimum  
Height  
2
0
Requirement  
Please refer to Page 11 (Exterior Vent Terminations)  
for additional guidelines on vent locations.  
66  
June 2007 Regency Product Specifications Book  
 
Gas Fireplaces  
P48 Gas Fireplace  
Horizontal Venting with Two (2) 90°  
Horizontal Venting with Three (3) 90°  
Elbows - Initial vertical section.  
Elbows - Initial vertical section.  
Two 45° elbows = One 90° elbow  
Two 45° elbows = One 90° elbow  
Option  
A)  
V
H+ H1  
3’ Max.  
4’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
8’ Max.  
Maximum total pipe: length, of  
all sections, must not exceed  
30 feet.  
Option  
A)  
V
H
V+ V1  
3’ Min.  
4’ Min.  
6’ Min.  
8’ Min.  
10’ Min.  
12’ Min.  
H + H1  
4’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
8’ Max.  
9’ Max.  
Maximum total  
pipe: length, of  
all sections, must  
not exceed 30  
feet.  
Total horizontal  
sections must not  
exceed 8 feet.  
Minimum of 1  
foot between  
90° elbows is  
required.  
1’ Min.  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
6’ Min.  
2’ Min.  
3’ Min.  
4’ Min.  
5’ Min.  
6’ Min.  
7’ Min.  
1’ Max.  
2’ Max.  
3’ Max.  
4’ Max.  
5’ Max.  
6’ Max.  
Total horizontal sections must  
not exceed 8 feet.  
B)  
B)  
C)  
C)  
Minimum of 1 foot between  
90° elbows is required.  
D)  
D)  
E)  
E)  
F)  
F)  
Horizontal Venting with Two (2) 90°  
Elbows - Initial horizontal section.  
Two 45° elbows = One 90° elbow  
Option  
A)  
H
V
H + H1  
3’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
8’ Max.  
Maximum total pipe: length, of  
all sections, must not exceed  
30 feet.  
Horizontal Venting with Three (3) 90°  
Elbows - Initial horizontal section.  
Two 45° elbows = One 90° elbow  
1’ Max.  
2’ Max.  
3’ Max.  
4’ Max.  
5’ Max.  
1’ Min.  
2’ Min.  
4’ Min.  
6’ Min.  
8’ Min.  
Total horizontal sections must  
not exceed 8 feet.  
B)  
C)  
Minimum of 1 foot between  
90° elbows is required.  
Option  
A)  
H
V
H + H1 + H2 Maximum total pipe:  
D)  
length, of all sections,  
E)  
1’ Max.  
2’ Max.  
3’ Max.  
4’ Max.  
5’ Max.  
6’ Max.  
1’ Min.  
3’ Min.  
5’ Min.  
7’ Min.  
9’ Min.  
11’ Min.  
3’ Max.  
5’ Max.  
6’ Max.  
7’ Max.  
8’ Max.  
9’ Max.  
must not exceed 30  
feet.  
B)  
Total horizontal sections  
must not exceed 7  
feet.  
C)  
Minimum of 1 foot  
between 90° elbows  
is required.  
D)  
E)  
F)  
June 2007 Regency Product Specifications Book  
 
67  

QSC Audio Car Amplifier DCA 1222 User Guide
Quantum Data Portable Generator 700, 701 User Guide
Radica Games Handheld Game System N5454 User Guide
Rheem Water Heater RH DV50FV User Guide
Roberts Radio Radio R9944 User Guide
Rowenta Electric Heater 029659 38 02 FR050 User Guide
Samsung Digital Camera A502 User Guide
Samsung Refrigerator SR 40NMA User Guide
Samsung Security Camera SPD 2700 User Guide
Sanyo Tool Storage CVW EXA124 User Guide